The power chain, second by second.
Proof the racks rode through.

The EPMS polls every switchboard, UPS, and PDU in the power chain as often as once a second, from the utility intake to the rack. Trends show drift before it becomes an outage, and every alert is tied to the equipment tag that raised it.

Live demo
Sample data. We draw your one-line from your electrical drawings and device list at onboarding.
MOD-03 / Power one-line
14:02:08Live

All feeds normal. Load on UTIL-1 through ATS-1. Batteries full.

Sequence of events

1 s resolution · 0 events
  1. No events. Load on UTIL-1, all feeds normal.

UPS-A

SNMP · every 1 s · read 14:02:08

Double conversion UPS · 250 kVA, Li-ion string

Mode
Online
Input voltage
480 V
Output voltage
480 V
Load
38%
Output power
95.0 kW
Battery
100%
Runtime left
14:20
Time on battery
0 s
Event recorder
1 s samples

The outage plays once as the one-line comes into view. Drop the utility to run it again, click a device or a log line for its points, or drag the recorder to scrub.

Monitoring and control

The whole electrical plant on one screen

Operators find the fault and respond in minutes.

Live power flow diagrams
Single-line diagrams with live readings. Trace power from the utility intake to the IT load, by mouse or on a touch screen.
One-second polling
Every integrated device and parameter is polled and logged as often as once per second. Transients land in the log instead of vanishing between samples.
Predictive analytics
Measurements are trended over time, so a value that is drifting shows before it takes a feed down. Thresholds you set raise the alert.
Tag-based alerts
Each alert carries the tag of the equipment that raised it. One click lands on that component instead of a top-level summary.

24/7 monitoring, 500+ data points per second, and 99.99% uptime achieved.

Runtime at current loadMOD-03 · UPS-B · 26 weeks

MOD-03 / UPS-B Runtime at current load is 9:53, under the 10:00 you set. Raised 2 weeks ago.

Runtime at current load, MOD-03 UPS-B, weekly
WeekRuntime
25 weeks ago14:13
24 weeks ago13:55
23 weeks ago13:56
22 weeks ago13:55
21 weeks ago13:33
20 weeks ago13:32
19 weeks ago13:19
18 weeks ago13:20
17 weeks ago13:03
16 weeks ago12:59
15 weeks ago12:38
14 weeks ago12:37
13 weeks ago12:29
12 weeks ago12:10
11 weeks ago12:01
10 weeks ago11:43
9 weeks ago11:40
8 weeks ago11:29
7 weeks ago11:08
6 weeks ago10:58
5 weeks ago10:38
4 weeks ago10:30
3 weeks ago10:11
2 weeks ago9:53
1 week ago9:43
This week9:23

Sample data. Runtime at current load, read from the UPS and trended weekly. Hover or use the arrow keys to read a week.

Power chain

The whole power chain

Every stage from utility intake to rack distribution, and what the EPMS reads at each.

Utility intake
  1. MDSMain Distribution Switchgear

    Utility intake metering, load balance across feeds, and redundancy status.

  2. GPSGenerator Paralleling Switchgear

    Generator status and automatic transfer switch position.

  3. UPSUninterruptible Power Supply

    Battery health, runtime, and load distribution.

  4. CRDSComputer Room Distribution Switchboards

    Row and zone power distribution.

  5. RPP and ePDURemote Power Panels and Power Distribution Units

    Rack metering, branch circuit monitoring, and outlet control.

A tag opens that device's points in the demo above.

Device integration

Protocols the power chain already speaks

Supported protocols are listed below. If a device needs a driver we do not have, we write one.

The node scans the network, finds devices, and matches them against a library of more than 46,000 make, model, and firmware versions. A device we have not seen before is onboarded within 48 hours at no cost.

Supported protocols
Modbus TCP and Modbus RTU
Over Ethernet and over serial lines
BACnet IP
Building Automation and Control Networks, over IP
OPC
OLE for Process Control
LON
Local Operating Network
SNMP
Simple Network Management Protocol
IPMI and proprietary protocols
Intelligent Platform Management Interface, and vendor protocols
Systems we integrate with

In the demo, UTIL-1, MSB-1, and the PDUs answer over Modbus TCP, ATS-1 and GEN-1 over Modbus RTU, and the UPS units and rack PDUs over SNMP.

Engineering

Engineering and implementation

Installation is straightforward and support is included.

One Aravolta node per module reads the whole power chain. We draw your one-line from your electrical drawings at onboarding.

ImplementationOne node per module
Hardware
Vendor agnostic. We work with whatever hardware is already on site.
Data points
Add as many points as you want. There is no per-point charge.
Network
Outbound connection only. No open inbound ports and no firewall rule changes.

See the EPMS on your module

Book 30 minutes with an engineer. Bring your one-line and we will walk through what the system reads at each stage.